2011 Reported Outages
December 2011
No outages reported.
November 2011
No outages reported.
October 2011
No outages reported.
September 2011
Datacenter unplanned power outage
Dates: 09-08-11 (5:15pm) through 09-09-11 (7:15am)
Length of outage: Approx 14 hours
Reason: SDGE general outage and Datacenter generator failure due to a bad water pump. The generator worked as expected only 10 minutes then failed. From that point the Datacenter ran approx 48 minutes on UPS power prior to complete outage. The water pump has since been replaced and the generator is functional once more.
If you have questions, email Edgar Hodge, Director of University Computer Operations (UCO) at ehodge@mail.sdsu.edu.
August 2011
E-mail Storage Maintenance:
(Planned outage)
Dates: 8/7/11 (10 am - 4pm)
Length of outage: Approx. 6 hours
Reason: Required maintenance
If you have questions, e-mail Edgar Hodge, Director of University Computer Operations (UCO) at ehodge@mail.sdsu.edu.
Note: During this time, access to mail.sdsu.edu/ webmail.sdsu.edu via pop/ imap/ webmail was not available. Incoming email messages were queued and resumed delivery after maintenance was completed.
July 2011
Meeting Maker:
(Planned outage)
Dates: 7/16/11 (2 am) through 7/17/11
Length of outage: Approx. 2 days
Reason: Maintenance to reduce size of database to improve application functionality
Contact email or phone:
etshelpdesk@mail.sdsu.edu
Resolution: Reduced the Meeting Maker database from 13 years of data down to 3 years
Note: Upon opening Meeting Maker for the first time after scheduled maintenance, users were instructed to click on Revert button option.
Power outage
Dates: 7/15/11 (11:35 pm) through 7/16/11 (2:15 am)
Length of outage: Approx. 3 hours
Reason: Campus lost power
Contact email or phone:
etshelpdesk@mail.sdsu.edu
Resolution: Power was restored by Physical Plant.
Note: UCO Data Center automatically switched over to UPS system.
June 2011
No outages reported.
May 2011
Network outage
Dates: 5/18/11 (7:08 am through 10 am)
Length of outage: Approx. 3 hours
Reason: Network down in Student Services West (approx 40 users affected)
Contact email or phone:
network@sdsu.edu
Resolution: TNS replaced a failed switch.